Demo data. Fictional facility. Nothing here is live.
Priority · RoutineClosed Wed 12:23

Everything that happened

3 done · 0 planned

Sun Oct 25

  1. Intakeagent
    Opened WO-1324: AHU-10: supply fan belt slipping (routine priority).
    Agent reported
  2. Diagnosticsagent
    Mono (AI) check at Marta R. request (0.9 inH2O reported; asset not named). Matched to SEN-AHU10-SP. Latest 0.92 inH2O at 02:15Z (quality ok); normal 1.2-1.8, min limit 1.0. Trend: 1.49-1.54 until about 23:05Z on 10-25, fell to 0.99 by 00:45Z, flat 0.92-0.94 since about 01:15Z. Other AHU SP sensors read 1.45-1.52. Existing WO-1324 (open, routine): supply fan belt slipping, suspected, not confirmed. No changes made. Room status not assessed.
    Agent reported

Mon Oct 26

  1. Diagnosticsagent
    Mono (AI) check at Marta R. request (0.8 reported). Matched to SEN-AHU10-SP, AHU-10. Latest 0.84 inH2O at 09:20Z (quality ok). Normal 1.2-1.8; min limit 1.0, below since about 00:40Z 10-26. Trend: 1.49-1.54 until about 23:10Z 10-25, fell to 1.00 by 00:40Z, low 0.92 near 01:25Z, 0.82-0.88 since 03:40Z, not recovered. FAN running; CCV 38%; FDP 0.73. Open WO-1324 (suspected belt slip, not confirmed). Room status not assessed. No changes made.
    Agent reported
  2. Now · Fri 20:23 (demo time)

How Mono handled this

Loading what Mono did.

The plan

No plan yet.

Mono will propose a new slot and vendor, and ask you before spending over its limit (demo).

Documents

Synthetic

No documents on this work order.